250 kW Commercial Rooftop Solar PV — Supply-Side Interconnection

Tipo Diagrama unifilarNorma IEEE Std 315 + ANSI device numberingMotor schematex-sldActualizado 6/10/2026
250 kW Commercial Rooftop Solar PV — Supply-Side Interconnection
Drawing preview
El escenario

A distribution center with a 480V service adds a 250 kW rooftop PV system. To avoid replacing the main service disconnect, the PV is interconnected on the supply side of that disconnect.

Qué hay en este dibujo

Lee las decisiones que hay detrás.

01

Use a supply-side tap point on the line side of the main service disconnect

02

Route PV through a production meter and dedicated 400 A AC disconnect

03

Keep feeder breakers and loads on the main switchboard downstream of the main service disconnect

Use for commercial rooftop PV projects where the PV output must land ahead of the main service disconnect, typical for load-side limitations or utility supply-side interconnection rules.