Industrial plant double-ended switchgear single line diagram

This feeder distribution single line diagram represents a double-ended 480 V switchgear lineup for an industrial plant. Two 2500 kVA transformers each feed a 3200 A main and their own bus section. A normally open 3200 A tie breaker links the sections for a planned maintenance or contingency transfer.

UPDATED 2026-09-23
EXAMPLEIndustrial plant double-ended switchgear single line diagram
Make this diagram your own.

Open it in the AI editor with a prompt pre-filled — keep what works, change what doesn't.

CASE ANALYSIS

Scenario

This industrial switchgear arrangement divides plant distribution across two transformer-fed buses, with a normally open bus tie for maintenance or contingency transfer.

Key decisions

  • Dual transformers: Two 2500 kVA sources supply independent 480 V bus sections.
  • Normally open tie: The 3200 A tie permits a controlled transfer without paralleling sources.
  • MCC feeder: A dedicated 800 A feeder serves motor control equipment.
  • Process segregation: The high-demand process line is fed from Bus A.
  • Utilities separation: Plant utilities stay on the separate Bus B section.

When to reuse this

Use this for a medium industrial facility needing maintainable LV distribution. Protection settings, source impedance, and transfer interlocking need coordination studies.

FAQ

Frequently asked questions

Why is the tie breaker normally open?01
It keeps the transformer sources separated during ordinary operation while preserving a transfer path.
Can one transformer carry both buses?02
Only if its loading, protection, and the transfer procedure have been engineered for that condition.
What is an MCC?03
A motor control center groups starters and protective devices for multiple motors.