PLC Relay Output Wiring for 120VAC Hydraulic Valve

סוג תרשים מעגלתקן IEEE Std 315 / ANSI Y32.2מנוע schematex-circuitעודכן 29.9.2026
PLC Relay Output Wiring for 120VAC Hydraulic Valve
Drawing preview
התרחיש

A PLC relay output energizes a 24VDC interposing relay coil; its normally open contact switches 120VAC to a hydraulic directional control valve solenoid.

מה מופיע בתרשים הזה

פענחו את ההחלטות שמאחוריו.

01

Use an interposing relay to isolate the PLC output from the 120VAC solenoid load.

02

Include a slow-blow fuse on the hot line to protect the solenoid circuit.

03

Keep the 24VDC control return isolated from the AC neutral.

Reuse when a PLC discrete output must drive a higher-voltage solenoid valve with galvanic isolation and fused protection.