ChatDiagram
Switchgear · Low voltage · Power distribution

480 V double-ended low-voltage switchgear

This double-ended low-voltage switchgear single line diagram shows two independent 13.8 kV sources transformed to separate 480 V bus sections. Each section has a 3200 A main breaker and supplies its own motor control center feeder. A normally open bus tie provides a planned transfer path when one source is unavailable.

Tipo Schema unifilareStandard IEEE Std 315 + ANSI device numberingMotore schematex-sldAggiornato 22/09/2026
480 V double-ended switchgear
Drawing preview
La richiesta

“Draw a 480 V double-ended switchgear single-line diagram with two 13.8 kV utility feeders, two 2000 kVA transformers, 3200 A mains, split Bus A and Bus B, a normally open bus tie, and two 800 A MCC feeders.”

Prova alloraAdd a generator tie breaker.Change both transformers to 2500 kVA.
Cosa contiene questo disegno

Leggi le decisioni che ne stanno alla base.

01

Each 13.8 kV feeder has a dedicated 2000 kVA transformer.

02

Both 480 V mains are rated 3200 A and 65 kA.

03

The bus tie is normally open to avoid paralleling sources.

04

Each bus supplies an independent 800 A MCC feeder.

Use this topology for plants that need sectionalized low-voltage distribution. Interlocking and transformer capacity must be verified before closing the tie.

Sfoglia tutti i modelli di tipo schema unifilare →

FAQ

Domande frequenti

Why is the bus tie normally open?

It keeps the two transformer sources separated during normal operation.

Can one transformer feed both buses?

It may during a transfer if transformer capacity and interlocking allow it.

What is an MCC feeder?

It is an outgoing circuit that supplies a motor control center.