ChatDiagram
Electrical Engineering · Industrial Control · Relay Logic

2-Relay Interface PNP-NPN Motor Start-Stop

유형 회로도표준 IEEE Std 315 / ANSI Y32.2엔진 schematex-circuit업데이트됨 2026. 9. 13.
2-Relay Interface PNP-NPN Motor Start-Stop
Drawing preview
상황

A 24Vdc motor start/stop interface uses a PNP transistor and START pushbutton to energize two relay coils; K1 seals the START command while K2 drives an NPN transistor that switches the contactor coil.

이 도면에 담긴 내용

그 이면의 의사결정을 읽어 보세요.

01

K1 seal contact is wired across the START pushbutton to latch the run command until STOP opens the coil path

02

K2 NO contact supplies Q2 base current through R3, keeping the NPN contactor driver isolated from the relay coil circuit

03

D1 across the K3 contactor coil clamps inductive kickback and protects Q2

Use this wiring when converting a 24Vdc PNP start/stop input into an NPN low-side output for a motor contactor in a control panel.