Mains-Generator Changeover Interlock

유형 회로도표준 IEEE Std 315 / ANSI Y32.2엔진 schematex-circuit업데이트됨 2026. 8. 22.
Mains-Generator Changeover Interlock
Drawing preview
상황

Two contactors are used in a changeover system to prevent mains and generator supplies from being connected simultaneously. A pushbutton start circuit with normally closed auxiliary contacts provides electrical interlock, while a mechanical interlock prevents both contactors from closing at once.

이 도면에 담긴 내용

그 이면의 의사결정을 읽어 보세요.

01

Use normally closed auxiliary contacts of each contactor in series with the opposite contactor coil for fail-safe electrical interlock.

02

Implement separate pushbutton start controls for mains and generator modes.

03

Label contactor symbols clearly with KM1 and KM2 reference designators.

Reuse this pattern for any dual-supply transfer system where back-feeding or source paralleling must be avoided, such as standby generator panels, UPS bypass, or solar/grid changeover.