ChatDiagram
PLC Programming · Ladder Logic · HVAC Controls

Cooling Tower Fan HOA Starter Logic

Tipo Lógica de escaleraNorma IEC 61131-3 Ladder DiagramMotor schematex-ladderActualizado 26/8/2026
Cooling Tower Fan HOA Starter Logic
Drawing preview
La solicitud

“Create a cooling tower fan HOA ladder with auto selection and enable, hand or auto motor command, overload protection, overload alarm, and run feedback.”

Entonces pruebaAdd a high-temperature auto request.Change the run lamp to a fault lamp.
Qué hay en este dibujo

Lee las decisiones que hay detrás.

01

Use an internal bit M0 for the auto request so the Fan Command output Y0 is driven by only one coil.

02

Place the overload trip XIO after the Hand/Auto parallel branches so it unconditionally stops the fan.

03

Add separate alarm and run-feedback outputs for operator visibility.

Use when converting a hardwired HOA motor starter to PLC control where auto-mode permissives and overload protection must be enforced before the motor output.

Explorar todas las plantillas de lógica de escalera →