ChatDiagram
PLC Programming · Ladder Logic · HVAC Controls

Cooling Tower Fan HOA Starter Logic

Tipo Lógica ladderNorma IEC 61131-3 Ladder DiagramMecanismo schematex-ladderAtualizado 26/08/2026
Cooling Tower Fan HOA Starter Logic
Drawing preview
A solicitação

“Create a cooling tower fan HOA ladder with auto selection and enable, hand or auto motor command, overload protection, overload alarm, and run feedback.”

Depois, tenteAdd a high-temperature auto request.Change the run lamp to a fault lamp.
O que há neste desenho

Entenda as decisões por trás dele.

01

Use an internal bit M0 for the auto request so the Fan Command output Y0 is driven by only one coil.

02

Place the overload trip XIO after the Hand/Auto parallel branches so it unconditionally stops the fan.

03

Add separate alarm and run-feedback outputs for operator visibility.

Use when converting a hardwired HOA motor starter to PLC control where auto-mode permissives and overload protection must be enforced before the motor output.