A 480 V industrial plant needs power factor correction and must avoid resonance with 5th and 7th harmonics; a detuned capacitor bank with series reactors provides compensation while shifting resonance below the harmonic orders.

What is in this drawing

Read the decisions behind it.

01

Use 7% detuned reactors to shift resonant frequency below the 5th harmonic

02

Wye-connected capacitor bank with grounded neutral for 277V phase voltage

03

Include discharge resistors across capacitors for safety

Reuse for industrial power factor correction where non-linear loads generate 5th/7th harmonics and detuned banks prevent harmonic amplification.