상황
A 480 V industrial plant needs power factor correction and must avoid resonance with 5th and 7th harmonics; a detuned capacitor bank with series reactors provides compensation while shifting resonance below the harmonic orders.
이 도면에 담긴 내용
그 이면의 의사결정을 읽어 보세요.
01
Use 7% detuned reactors to shift resonant frequency below the 5th harmonic
02
Wye-connected capacitor bank with grounded neutral for 277V phase voltage
03
Include discharge resistors across capacitors for safety
Reuse for industrial power factor correction where non-linear loads generate 5th/7th harmonics and detuned banks prevent harmonic amplification.