ChatDiagram
BESS · Peak shaving · Commercial

500 kW commercial peak-shaving BESS

This commercial BESS single line diagram shows a 500 kW, 1 MWh lithium iron phosphate storage system connected to an office-campus main switchboard. The bidirectional power conversion system charges from the 480Y/277 V bus and discharges to reduce utility demand during selected peaks. A feeder breaker provides the AC connection, while the battery enclosure is shown on the DC side of the PCS.

Type Single-line diagramStandard IEEE Std 315 + ANSI device numberingEngine schematex-sldUpdated 9/22/2026
Commercial peak-shaving BESS
Drawing preview
The request

“Draw a single-line diagram for a 480Y/277 V office campus with a 1.2 MW load and a 500 kW, 1 MWh LFP battery connected through a bidirectional PCS and 800 A feeder breaker for peak shaving.”

Then tryAdd rooftop solar.Change the PCS to 750 kW.
What is in this drawing

Read the decisions behind it.

01

The demand meter is upstream of the main switchboard so imported demand is visible.

02

A 500 kW PCS connects through an 800 A feeder breaker.

03

The battery enclosure is rated 1.0 MWh at 1000 Vdc.

04

The e-stop and fire interlock is shown as a dedicated safety input to the PCS.

This is suitable for behind-the-meter demand management where export is not the main objective. Site fault duty, fire code, and utility control requirements must be checked.

More like this

Other examples in this family.

Browse all single‑line diagram templates →

FAQ

Common questions

What is peak shaving?

The battery discharges during high demand intervals to reduce power imported from the utility.

Why use LFP cells?

Lithium iron phosphate is commonly selected for stationary storage because of its thermal and cycle-life characteristics.

Can this system export power?

It can if approved and configured for export, but this drawing focuses on behind-the-meter load reduction.