Commercial solar PV interconnection — Single Line Diagram

This commercial solar PV interconnection single-line diagram follows the power path from a 250 kWdc PV array to a 480 V main switchboard. The array feeds a 600 Vdc combiner, then a DC disconnect and a labeled 200 kWac grid-tie inverter. On the AC side, power passes through a 480 V, 400 A disconnect and production meter before reaching the main switchboard. The utility also feeds that switchboard, making the point of interconnection clear.

Type Single-line diagramStandard IEEE Std 315 + ANSI device numberingEngine schematex-sldUpdated 9/24/2026
Commercial solar PV interconnection
Drawing preview
The request

“Draw a commercial solar PV interconnection single-line with a 250 kWdc PV array, 600 Vdc combiner and DC disconnect, 200 kWac grid-tie inverter, 480 V 400 A AC disconnect, production meter, main switchboard, and utility.”

Then tryAdd an AC feeder breaker at the main switchboard.Change the inverter rating to 250 kWac.
What is in this drawing

Read the decisions behind it.

01DC collection

The 250 kWdc PV array lands at a 600 Vdc combiner before the DC disconnect.

02AC conversion

A labeled 200 kWac grid-tie inverter converts the array output for the 480 V system.

03Accessible isolation

Separate DC and 480 V, 400 A AC disconnects identify the isolation points on each side of the inverter.

04Metered interconnection

The production meter sits between the AC disconnect and the main switchboard, which is also utility-fed.

Use this one-line for a basic commercial grid-tied PV concept. Complete designs need code-required protection, rapid shutdown, grounding, utility interconnection, and equipment-specific details.

More like this

Other examples in this family.

Browse all single‑line diagram templates →

FAQ

Common questions

Why is the PV array rated in kWdc and the inverter in kWac?

PV modules produce DC power, while the grid-tie inverter outputs AC power to the building electrical system.

What does the DC combiner do?

It combines PV source circuits into a common DC output before the DC disconnect and inverter.

Why is there a production meter?

It measures PV energy production separately from the site’s utility meter or building consumption.

Is the 400 A AC disconnect the only required protection?

No. Final protection and disconnecting means depend on code, inverter instructions, switchboard ratings, and utility requirements.