VFD Motor Control Single Line Diagram

This VFD motor control single-line diagram shows a 400 V, three-phase, 50 Hz supply feeding a 75 kW induction motor through a variable-frequency drive. The incomer passes through a 200 A main isolator and 200 A main circuit breaker to a 400 V busbar. A dedicated 160 A feeder breaker then supplies the 160 A VFD. The drawing identifies 70 mm² copper cable on both the VFD input and motor output sides.

Type Single-line diagramStandard IEEE Std 315 + ANSI device numberingEngine schematex-sldUpdated 9/24/2026
VFD Motor Control Single Line Diagram
Drawing preview
The request

“Draw a 400 V, three-phase 50 Hz supply through a 200 A isolator, 200 A main breaker, and busbar to a 160 A VFD feeder and 160 A VFD driving a 75 kW induction motor, with 70 mm² copper input and motor cables.”

Then tryAdd a bypass contactor around the VFD.Change the motor rating to 55 kW.
What is in this drawing

Read the decisions behind it.

01Maintenance isolation

A 200 A main isolator precedes the main breaker for a visible upstream isolation point.

02Protected feeder

A dedicated 160 A breaker protects the VFD branch from the 400 V main busbar.

03Drive matching

The VFD is rated 160 A, appropriate for the approximate full-load current range of a 75 kW, 400 V motor.

04Cable indication

Both VFD input and motor output are shown as 70 mm² copper conductors, subject to installation derating.

Use this as a concept one-line for a 75 kW VFD motor branch. Final equipment ratings, cable sizes, protection settings, and harmonic measures require project-specific calculations.

More like this

Other examples in this family.

Browse all single‑line diagram templates →

FAQ

Common questions

Why is the VFD feeder rated 160 A?

A 75 kW motor at 400 V typically draws well above 100 A. The final rating must follow the motor and VFD manufacturer data.

Can 70 mm² copper always be used for this motor?

No. Ampacity and voltage drop depend on installation conditions, cable construction, ambient temperature, grouping, and local code.

Why is there an isolator ahead of the breaker?

It provides a local means of isolation for maintenance, subject to the selected device’s load-break and safety requirements.

Does this diagram show VFD control wiring?

No. It shows the power path only; start/stop, speed reference, interlocks, and safety wiring need a separate control schematic.