ChatDiagram
industrial-control · plc-interface · circuit

Relay Interface for PLC Input: PNP Sensor Coil Input, NPN Contact Output

Tipo Schema elettricoStandard IEEE Std 315 / ANSI Y32.2Motore schematex-circuitAggiornato 13/09/2026
Relay Interface for PLC Input: PNP Sensor Coil Input, NPN Contact Output
Drawing preview
Lo scenario

A 24 V PNP proximity sensor output must interface to an NPN-sinking PLC input; an interposing relay isolates the sourcing sensor from the sinking input.

Cosa contiene questo disegno

Leggi le decisioni che ne stanno alla base.

01

Use a relay with coil driven by the PNP output and a flyback diode across the coil

02

Wire the relay common to the PLC input and NO to 0 V so the closed contact sinks current from the PLC pull-up

Reusable for any PNP sensor to NPN PLC input conversion using a single interposing relay and DC coil supply.

Sfoglia tutti i modelli di tipo schema elettrico →