ChatDiagram
industrial-control · plc-interface · circuit

Relay Interface for PLC Input: PNP Sensor Coil Input, NPN Contact Output

유형 회로도표준 IEEE Std 315 / ANSI Y32.2엔진 schematex-circuit업데이트됨 2026. 9. 13.
Relay Interface for PLC Input: PNP Sensor Coil Input, NPN Contact Output
Drawing preview
상황

A 24 V PNP proximity sensor output must interface to an NPN-sinking PLC input; an interposing relay isolates the sourcing sensor from the sinking input.

이 도면에 담긴 내용

그 이면의 의사결정을 읽어 보세요.

01

Use a relay with coil driven by the PNP output and a flyback diode across the coil

02

Wire the relay common to the PLC input and NO to 0 V so the closed contact sinks current from the PLC pull-up

Reusable for any PNP sensor to NPN PLC input conversion using a single interposing relay and DC coil supply.

모든 회로도 템플릿 보기 →