University science laboratory distribution single line diagram

This university building single line diagram shows electrical distribution for a science laboratory. A 13.8 kV campus loop feeds a 2000 kVA transformer and 480Y/277 V laboratory switchboard. The normal bus supplies fume hood exhaust, a process chiller, and teaching laboratories. A 150 kVA UPS supplies a separate critical bus for analytical instruments.

種類 単線結線図規格 IEEE Std 315 + ANSI device numberingエンジン schematex-sld更新日 2026/9/22
Science laboratory distribution
Drawing preview
依頼内容

“Draw a university building single line diagram for a science laboratory with a 13.8 kV campus loop, 2000 kVA transformer, 480 V switchboard, 150 kVA research UPS, fume hood exhaust, process chiller, teaching lab, and analytical instrument feeders.”

次はこちらAdd an emergency generator to the research UPS path.Change the process chiller feeder to 800 A.
この図に含まれるもの

図の背後にある意思決定を読み解く。

01Campus connection

A 13.8 kV loop feeds a dedicated 2000 kVA laboratory transformer.

02Mechanical ventilation

Fume hood exhaust has a separate 400 A motor feeder.

03Process cooling

A 600 A feeder supplies the research chiller.

04Research continuity

A 150 kVA UPS feeds the instrument critical bus.

05Load separation

Teaching labs remain on a normal 300 A feeder.

Use this for a research or teaching laboratory building. Hazardous-process controls, emergency power, and lab equipment loads require further study.

単線結線図のテンプレートをすべて見る →

よくある質問

よくある質問

Why are analytical instruments on a UPS bus?

Sensitive instruments may need ride-through power during brief utility disturbances.

Why is fume hood exhaust separate?

It is a major safety-related mechanical load with its own feeder and controls.

Does the UPS power the chiller?

No. The high-demand process chiller remains on the normal switchboard in this example.