An electrical engineer preparing permit drawings for a new commercial building needs a feeder distribution SLD.
이 도면에 담긴 내용
그 이면의 의사결정을 읽어 보세요.
01
Two-busbar arrangement (A/B) allows either feeder bus to be de-energized independently for maintenance.
02
800 A feeder breakers sized to protect bus cable; 200 A load breakers provide downstream discrimination.
03
Main CB at 2000 A provides bus-fault protection coordinated with upstream HV fuse on the 11kV side.
Add a bus-coupler breaker between BUS_A and BUS_B to enable N-1 redundancy.