Medium Voltage Feeder Distribution SLD

A LV feeder distribution SLD from a 1500 kVA, 11kV/415V transformer through a 2000 A main circuit breaker to two feeder busbars, each feeding loads through 800 A feeder breakers and final 200 A distribution breakers.

Type Single-line diagramStandard IEEE Std 315 + ANSI device numberingEngine schematex-sldUpdated 5/27/2026
Feeder Distribution 415V SLD
Drawing preview
The scenario

An electrical engineer preparing permit drawings for a new commercial building needs a feeder distribution SLD.

What is in this drawing

Read the decisions behind it.

01

Two-busbar arrangement (A/B) allows either feeder bus to be de-energized independently for maintenance.

02

800 A feeder breakers sized to protect bus cable; 200 A load breakers provide downstream discrimination.

03

Main CB at 2000 A provides bus-fault protection coordinated with upstream HV fuse on the 11kV side.

Add a bus-coupler breaker between BUS_A and BUS_B to enable N-1 redundancy.