ELECTRICAL ENGINEERING

9.8 MW Refinery Waste-Heat Back-Pressure STG — 6.6 kV Industrial Cogeneration Plant SLD

A worked electrical engineering example, rendered live. Open it in the AI editor and adapt it to your own case.

UPDATED 2026-09-27
EXAMPLE9.8 MW Refinery Waste-Heat Back-Pressure STG — 6.6 kV Industrial Cogeneration Plant SLD
Make this diagram your own.

Open it in the AI editor with a prompt pre-filled — keep what works, change what doesn't.

CASE ANALYSIS

Scenario

A refinery captures waste heat to drive a 9.8 MW back-pressure steam turbine generator at 6.6 kV, operating in parallel with a 132 kV grid intake to supply process and auxiliary loads.

Key decisions

  • Use 132/6.6 kV 25 MVA grid transformer for grid infeed
  • Connect STG through dedicated 1250 A breaker and CT to the 6.6 kV main bus
  • Provide 6.6/0.4 kV auxiliary transformer for 400 V plant auxiliaries
  • Split 6.6 kV bus with a bus tie for standby/refinery feeder isolation

When to reuse this

Reuse for industrial cogen/CHP plants where a waste-heat STG, grid import, and multiple process/auxiliary feeders share a medium-voltage bus.