Das Szenario
A refinery captures waste heat to drive a 9.8 MW back-pressure steam turbine generator at 6.6 kV, operating in parallel with a 132 kV grid intake to supply process and auxiliary loads.
Was diese Zeichnung zeigt
Die dahinterstehenden Entscheidungen verstehen.
01
Use 132/6.6 kV 25 MVA grid transformer for grid infeed
02
Connect STG through dedicated 1250 A breaker and CT to the 6.6 kV main bus
03
Provide 6.6/0.4 kV auxiliary transformer for 400 V plant auxiliaries
04
Split 6.6 kV bus with a bus tie for standby/refinery feeder isolation
Reuse for industrial cogen/CHP plants where a waste-heat STG, grid import, and multiple process/auxiliary feeders share a medium-voltage bus.