9.8 MW Refinery Waste-Heat Back-Pressure STG — 6.6 kV Industrial Cogeneration Plant SLD

Type Single-line diagramStandard IEEE Std 315 + ANSI device numberingEngine schematex-sldUpdated 9/27/2026
9.8 MW Refinery Waste-Heat Back-Pressure STG — 6.6 kV Industrial Cogeneration Plant SLD
Drawing preview
The scenario

A refinery captures waste heat to drive a 9.8 MW back-pressure steam turbine generator at 6.6 kV, operating in parallel with a 132 kV grid intake to supply process and auxiliary loads.

What is in this drawing

Read the decisions behind it.

01

Use 132/6.6 kV 25 MVA grid transformer for grid infeed

02

Connect STG through dedicated 1250 A breaker and CT to the 6.6 kV main bus

03

Provide 6.6/0.4 kV auxiliary transformer for 400 V plant auxiliaries

04

Split 6.6 kV bus with a bus tie for standby/refinery feeder isolation

Reuse for industrial cogen/CHP plants where a waste-heat STG, grid import, and multiple process/auxiliary feeders share a medium-voltage bus.