1 MW Utility-Scale Solar PV Interconnection

Tipo Diagrama unifilarNorma IEEE Std 315 + ANSI device numberingMecanismo schematex-sldAtualizado 06/10/2026
1 MW Utility-Scale Solar PV Interconnection
Drawing preview
O cenário

Design review for a 1 MW utility-scale solar PV plant requiring a three-phase step-up transformer and utility interconnection at 12.47 kV.

O que há neste desenho

Entenda as decisões por trás dele.

01

Use transformer_dy for 480V to 12.47kV step-up with delta-wye isolation

02

Place revenue meter on MV side ahead of utility point of connection

03

Use switch_load for DC disconnect per NEC 690 isolation

04

Represent grid-tie inverter as generic load symbol pending dedicated static converter symbol

Reuse when drafting utility interconnection SLDs for behind-the-meter or export PV systems with transformer isolation and MV metering.